| |
( Printable Version )
Greenhouse Cooling Systems
Greenhouse glazing materials allow shorter wavelength radiation (i.e. visible light) to pass through but long wavelength radiation such as infrared (heat) is trapped inside the greenhouse. The temperature inside of a greenhouse may be up to 30° F higher than the ambient temperature outside of the greenhouse (hence, the greenhouse effect). Because of this property, greenhouses may require both summer and winter cooling systems.
Summer Cooling Systems
Passive venting
High summer temperatures result in the need for constant heat
removal from the greenhouse. This may be accomplished by replacing
existing air in the greenhouse with cooler air from outside of
the structure. If outside temperatures are low enough, and if
temperatures in the greenhouses are not too high, warm air may
be passively exhausted through roof
vents. The upward and outward movement of warm air pulls in
cool air from side or end vents. This system is most effective
in the winter, spring and fall. It is limited in its effectiveness
for summer cooling to high elevations (i.e. Colorado) and coastal
areas (i.e. Half Moon Bay, California) since the incoming solar
load and the outside air temperature may be too high for the capabilities
of this system during summer months in most other climates.
Shading Systems
Shading systems are another example of a passive cooling system
used in summer months (or the year around in tropical climates).
These systems may include white
latex shading, saran
cloth shading or retractable
shading systems. They all function by limiting the amount
of light energy entering the structure and thus reducing the solar
load.
Fan-and-Pad System
This is the most common type of active cooling system used in
commercial greenhouses. The system takes advantage of the latent
heat of evaporation. More specifically, as liquid water evaporates,
it absorbs energy from the environment (i.e. surrounding air).
This results in a lowering of the temperature of the surrounding
air. In a fan-and-pad system, cellulose
pads (or pads made of another material) are placed in
one
wall of the greenhouse and fans
are placed in the opposite wall. The fans exhaust air out of the
greenhouse. This creates
a vacuum inside of the greenhouse and causes air to enter
the greenhouse through the pads at the opposite end of the greenhouse.
All vents, except for the pad opening, are closed when the fan-and-pad
system is in operation. Water is
forced through the pads, and as air moves through the pads,
some of the water absorbs energy (heat) from the air as it evaporates.
This results in a cooling
of the air as it moves through the pad and into the greenhouse.
In a fan-and-pad cooling system, water
is supplied to the pad from a tank (sump) that serves
as a reservoir. A pump (such as a common sump pump) is used
to move water from the reservoir to the top of the pads. The water
is first supplied to a feed line that runs the length of the pads.
Holes in the top of the feed line allow water to be forced out
of the line. The water is forced upward, strikes a cover plate
and trickles down to the pads. A cover material may be placed
on the top of the pad to allow for more even wetting of the pad.
The water trickles down through the pad, is collected in a catch
basin and is recycled back to the reservoir. Because water evaporates
as it passes through the pads (1 gallon per minute can be lost
through 100 ft2 of pad on a hot dry day), water must
be continuously resupplied to the reservoir. This is accomplished
by having a water supply line to the reservoir that is controlled
by a floater. The reservoir should have a capacity large enough
to hold enough water to fill all pipes and saturate the pads.
The water supply system should operate so that the entire pad
is kept wet.
Pads need to be properly maintained. Salt buildup and algae
growth are the greatest threat to the longevity of the pads.
As water evaporates, salts accumulate on the pads. These deposits
physically block air movement through the pads and prevent uniform
wetting. If the water supply is high in salts, blended water should
be used. Algae can also accumulate on pads. Several biocides can
be added to the water to prevent algae growth. Sodium hypochlorite
(bleach) may be added at a rate of 1% by volume. This provides
a 3-5 parts-per-million Cl- solution. However, the
bleach will tend to cause the water pH to increase, and this can
damage pads by softening the glue holding together the pad layers.
Calcium hypochlorite (i.e. pool bleach) and Agribrom® are
preferred biocides for use with a fan-and-pad cooling system.
Positive pressure coolers
are essentially self-contained fan-and-pad cooling systems with
the pads and fan contained within an enclosed unit. The fan used
is a squirrel cage fan and is located within the cooling unit.
The fan forces air out of the cooling unit and into the greenhouse,
thus creating a vacuum inside of the unit and drawing air into the unit. On the inside
of the vents of the cooling unit are water-saturated
pads. The air is pulled through these pads as it enters the
cooling unit and the air
is cooled. Sometimes these units are mounted outside the gable
of the greenhouse and the cooled air is forced into a polyethylene
tube that extends the length of the house. Because air is being
forced into the greenhouse (the vacuum is inside the cooing unit),
this type of cooling is often called positive pressure cooling
because positive pressure is created inside the greenhouse (fans forcing air into greenhouse).
These systems (Mee
Fog® systems are common examples) use evaporative cooling
just as the fan-and-pad system. However, with these systems, very
small droplets (approximately 0.04 inches in diameter) of water
are forced into the air. Because of the small size of the droplets,
they remain suspended in the air (and thus do not wet the plant
material). The droplets evaporate while suspended in the air,
thereby cooling the air through evaporation. The water-saturated
air is slowly removed from the greenhouse through roof vents or
low-volume fans mounted in the greenhouse walls. These systems
require some specialized equipment and are most useful for cooling
structures used in propagation, seed germination and plug production.
Outside of these situations, fog-cooling systems are not commonly
used in the U.S., but they are common in Canada and Europe.
Winter Cooling Systems
In some areas of the country, high light levels or fluctuating
temperatures might necessitate cooling even during winter days.
Additionally, during early spring and late fall months, heating may be required
at night and early mornings while some cooling may be required
during the day when solar loads are high. Passive venting as discussed
above is one method that may be used for this type of cooling
need. However, if the solar load is too high, an active cooling
system may be required to increase the rate at which warm inside
air is replaced with cool air from outside of the greenhouse. In
this situation, the top vent may be closed and fans
in the greenhouse walls activated. Louvered
vents in the opposite walls open to allow air to move into
the greenhouse. The fans may be multi-speed fans so that just
enough air is exhaust from the greenhouse (an replaced with outside
air) to maintain the desired temperature. If temperatures continue
to increase, the fan speed can be increased.
Another method used for winter cooling utilizes fans
placed in the gable of the greenhouse and combined with a
polyethylene
tube extended the length of the greenhouse in the gable. The
inlet
vent is louvered and opens only when the fans turn on. There
is an additional set of louvered vents at the opposite end of
the greenhouse that allows warm greenhouse air to escape while
cooler outside air is forced into the structure. The cool air
is forced through the polyethylene tube to allow for a more even
distribution of the cool air. In some cases, a unit heater may
be used in conjunction with this system. The unit heater is placed
in front of the louvered inlet. If heat is needed, the louver
and vents are closed. The heater draws in air from within the
greenhouse, heats it and forces the warm air through the polyethylene
distribution tube. If cooling is needed, the louvered vent and
exhaust vent open, and the unit heater fan turns (without ignition
of the flame) on to force cool air form outside into the polyethylene
tube.
Calculating Greenhouse Cooling Requirements
To determine specifications for cooling system, the greenhouse volume must be determined, and based upon several assumptions a flow rate per minute (air exchanges) requirement is determined.
As example, cooling specifications are outlined below for a quonset greenhouse that is 30 ft wide and 110 ft in length.
The volume of the structure is determined as: 0.5(πr2L)
= 0.5[(3.14)(152)(110)]
= 38,857 ft3
An air exchange of 1 to 1.5 times per minute is required. The value of 1.5 would be used if the greenhouse were to be used during summer months where very high solar loads and temperatures will be experienced. In this example, 1 exchange per minute is used so that 38,857ft3/min (cfm) is required.
Fans should be space not greater than 25 ft apart. Therefore, this structure requires two fans space along the 30 ft wall. The structure will therefore require two fans with a capacity of (38,857cfm/2) 19,429 cfm. From the list of fan specifications, two 48-inch, 1 horsepower fans are selected. These fans provide a total of 39,200 cfm.
Aspen pads, 4-inch or 6-inch cellulose pads could be included to create a fan-and-pad cooling system. In this example, 4-inch cellulose pads are included. One square foot of this type of pad will accommodate 250 cfm. Therefore, 39,200 cfm/250 = 157 ft2 of pad wall is required. The pad wall should extend the entire length of the way. Therefore the pad should be 30 ft wide and (157 ft2/30ft) 5.2 ft tall.
The pump capacity must take into account the volume of water flow required by the system (pipes and pads) as well as water loss through evaporation from the pads.
To accommodate the system, 0.50 gallons are required per linear foot per minute. Therefore, 30 ft x 0.5 gallons/ft = 15 gallons to accommodate the system.
To compensate for evaporation, 0.05 gallons are required per 1000 cfm of airflow. Therefore, (39,200 cfm/1000 gallons/cfm)0.05 = 2 gallons required to compensate for evaporation.
The total pump capacity is 15 gallons + 2 gallons = 17 gallons.
The sump capacity is determine as 157 ft2 of pad x 0.75 gallons/ft2 of pad = 118 gallons.
|
Air Delivery Capacities for Various Greenhouse Fan Dimensions and Motors |
|
Fan Size (inches) |
Motor (horsepower) |
Feet3/min (cfm) at 0.1 inch static pressure |
|
24 |
1/4 |
4,500 |
|
24 |
1/3 |
5,700 |
|
24 |
1/2 |
6,500 |
|
24 |
3/4 |
7,600 |
|
30 |
1/3 |
7,400 |
|
30 |
1/2 |
8,800 |
|
30 |
3/4 |
10,200 |
|
36 |
1/3 |
8,800 |
|
36 |
1/2 |
10,600 |
|
36 |
3/4 |
12,700 |
|
36 |
1 |
14,200 |
|
42 |
1/2 |
12,500 |
|
42 |
3/4 |
15,000 |
|
42 |
1 |
16,800 |
|
48 |
1/2 |
14,700 |
|
48 |
3/4 |
17,800 |
|
48 |
1 |
19,600 |
|
54 |
1 |
22,900 |
|
54 |
1 1/2 |
25,800 |
|
Specifications for Design of Pad Wall for Fan-and -Pad Greenhouse Cooling System |
|
Pad type |
Airflow required (exchanges/min) |
Ft3 flow accommodated per ft2 of pad |
Water flow rate (gallons per minute per linear ft) |
Water loss rate (gallons per minute per 1000 cfm of air flow) |
Sump capacity (gallons/ft2 of pad) |
|
Aspen |
1 to 1.5
|
150 |
0.30 |
0.05 |
0.50 |
|
4" cellulose |
1 to 1.5 |
250 |
0.50 |
0.05 |
0.75 |
|
6" cellulose |
1 to 1.5 |
350 |
0.75 |
0.05 |
1.00 |
Integration of Cooling Systems
During spring and fall, temperatures are cool at night and increase during the day due to the solar load. During these seasons, the cooling system may be integrated so that as the temperature reaches a certain set point (set by the greenhouse manager), the roof and side vents open to allow for passive venting. If the temperature continues to increase, the roof and side vents close, the louvered vents opposite the fans open, and the fans turn on to actively bring in cooler air from outside. If the temperature continues to increase, the sump pumps associated with the pads turn on and begin feeding water to the pads to lower the temperature of the air entering the greenhouse and to increase the cooling potential. This cyclic or integrated approach helps to reduce energy costs.
Read the article "Fan and Pad Greenhouse Evaporative Cooling Systems"
Read the article "Fans for Greenhouses"
Read the article "Auxiliary Power Units for Greenhouse Operations"
© 2005, M.R. Evans
|