Mainframe Equipment Electrical and Cooling Requirements
(DRPMS102)

Last update: Tuesday, 21-Mar-2000 10:34:37 CST

This document contains the detailed electrical and cooling specifications for the mainframe equipment that is to be assembled at the BELL 108 Cold Site. This information is needed by electricians to determine the type of circuit breaker, electrical cable, and power connector for each piece of equipment. The cooling specifications can be summed to produce the cooling capacity required for this equipment and to determine how much air conditioning is needed.

Vendor Device
Type
Qty Volts Cycles Phase kVA Circuit
Breaker
Rating
Power
Receptacle
Cooling
(BTU/hr)
Notes
HDS GX6425 1 208V 60 Hz 3 27.25 75A x 2 RS JCS1034H 81,959 Two receptacles/breakers required
HDS Console 1 110V 60 Hz 1 0.2 15A NEMA 5-15R 478  
HDS 7690 1 208V 60Hz 1 1.4 15A x 2 RS 3913 4,436 Two receptacles/breakers required
HDS 7693-32 2 208V 60 Hz 1 2.44 30A RS 3934 8,053  
IBM 3880-G23 3 208V 60 Hz 3 3.3 15A RS 3744 * 9,900  
IBM 3380-AE4 4 208V 60Hz 3 3.3 40A RS 7324-78 * 9,900  
IBM 3380-BE4 9 n/a n/a n/a 2.8 n/a n/a * 8,400  
IBM 3274-41D 5 208V 60 Hz 1 0.3 15A NEMA 6-15R * 900  
IBM 3174-01L 1 110V 60 Hz 1   15A NEMA 5-15R    
IBM 3192-C10 12 110V 60 Hz 1   15A NEMA 5-15R    
BTI ELC2 1 110V 60 Hz 1   15A NEMA 5-15R    
BTI ELC3 1 110V 60 Hz 1   15A NEMA 5-15R    
IBM 3480-A22 2 208V 60 Hz 3 1.0 30A RS 3754 * 3,000  
IBM 3480-B22 8 n/a n/a n/a 0.8 n/a n/a * 2,400  
IBM 3160-001 1 208V 60 Hz 1 2.1 15A NEMA 6-15R * 6,300  
IBM 6262-014 1 110V 60 Hz 1 1.5 15A NEMA 5-15R 2,700  
IBM 3268-002 1 110V 60 Hz 1   15A NEMA 5-15R    
IBM 3088-002 1 208V 60 Hz 1 1.2 15A RS 3913U2 * 3,600  

* These BTU values are estimates.


Mainframe BTU Totals

Total BTUs (From Above Table) 290,179
Total BTUs For Unknowns (Estimated) 10,000

Total BTUs For Mainframe Equipment 300,179


Mainframe kVA Load Totals

Total kVA (From Above Table) 96.7
Total kVA For Unknowns (Estimated) 3.5

Total kVA For Mainframe Equipment 100.4